| Certification Vendor: | Huawei |
|---|---|
| Exam Name: | HCSP-Field Data Center Facility V1.0 Certification Exam |
| Exam Number: | H20-923_V1.0 |
| Certificate Validity Period: | 3 years |
| Exam Format: | Multiple Response, Multiple Choice |
| Real Exam Qty: | N/A |
| Passing Score: | N/A |
| Exam Duration: | N/A |
| Related Certifications: | HCSP-Field HCIE-Field HCSA-Field |
| Exam Price: | N/A |
| Available Languages: | Chinese, English |
| Recommended Training: | Data Center Facility Fundamentals Learning Path HCSP-Field Training Courses |
| Exam Registration: | Huawei Talent Online |
| Sample Questions: | Huawei H20-923_V1.0 Sample Questions |
| Exam Way: | Typically delivered via Pearson VUE authorized testing centers or online proctored exam depending on region. |
| Pre Condition: | Basic understanding of IT infrastructure and data center operations is recommended; no strict formal prerequisite publicly specified. |
| Official Syllabus URL: | https://e.huawei.com/en/talent/ |
H20-923_V1.0練習教材を購入したすべての学生は、HuaweiのH20-923_V1.0学習教材が提供する内容に従い、毎日学習する限り、プロのH20-923_V1.0資格試験に合格できると信じています。 模擬試験を通じて定期的に自己検査を実施します。 もちろん、Jpexam購入する前に、H20-923_V1.0学習教材は無料の試用サービスを提供します。当社のWebサイトにログオンしている限り、無料で試用版のHCSP-Field-Data Center Facility V1.0質問バンクをダウンロードできます。 H20-923_V1.0テストエンジンを試した後、あなたはそれらを愛することになると信じています。
| トピック | 出題範囲 |
|---|---|
| トピック 1 |
|
| トピック 2 |
|
| トピック 3 |
|
| トピック 4 |
|
| トピック 5 |
|
| トピック 6 |
|
| トピック 7 |
|
| トピック 8 |
|
| トピック 9 |
|
| トピック 10 |
|
| トピック 11 |
|
| トピック 12 |
|
| トピック 13 |
|
質問 # 14
In IT scenarios, which of the following are the power supply and distribution components of the FusionDC1000A?
正解:A、B、D
解説:
In the FusionDC1000A IT scenario, the power chain is built around an AC input, conditioned backup power, energy storage, and final distribution to the IT racks.Integrated UPSis the core power-conditioning component, providing voltage and frequency stabilization and uninterrupted supply during mains disturbances. The UPS works together withSmartLi, Huawei's lithium battery system, which serves as the energy storage unit to sustain the load during outages and to support controlled shutdown or generator switchover. After UPS output, power is delivered to the IT loads through thePower PDB, which performs downstream distribution, branch protection, and organized cable termination toward rack PDUs or IT equipment feeders. By contrast, anAC/DC power systemis typically associated with DC bus supply used in telecom-oriented or dedicated DC load scenarios, not the standard IT scenario architecture of FusionDC1000A that is centered on UPS plus battery plus AC distribution. Therefore, the correct components for IT scenarios are SmartLi, Power PDB, and Integrated UPS.
質問 # 15
The NetEco service program backend can be accessed through the iBMC port.
正解:B
解説:
In Huawei data center facility management,NetEcois the management software platform (server/application) used to centrally monitor and manage sites, whileiBMCis the out-of-band hardware management interface used forserver remote maintenance(such as power control, hardware health, BIOS settings, and remote console) on the specific server where iBMC exists. TheiBMC port is not a service access interface for NetEco. NetEco's backend services are accessed through theserver operating system network interfaces (management/service network) and corresponding application ports after the server is properly networked and configured. Even if NetEco is deployed on a Huawei server that has iBMC, iBMC only provides a channel to manage the server hardware and does not expose NetEco application access as an official commissioning
/O&M path. Therefore, NetEco backend access should be planned via the site's management network (IP addressing, routing, security policy), not via iBMC.
質問 # 16
What is the upstream input voltage range of the UPS5000-H?
正解:D
解説:
For the Huawei UPS5000-H (380/400/415 V class), "upstream input voltage range" refers to the acceptableAC mains (rectifier) line-to-line input voltage windowthat the UPS can tolerate while maintaining operation. Huawei specifies a wide mains input voltage range of138-485 Vac (line voltage)to improve adaptability to weak or fluctuating power grids and to reduce unnecessary battery usage when the utility voltage sags or rises within allowable limits. Within this overall window, the UPS may applyderating rulesat lower voltages (for example, full-load operation is typically guaranteed only above a higher threshold), but the upstream input can still remain connected and the UPS continues supplying the load according to its control strategy and available capacity. The other options do not match the upstream AC input range:360-600 Vis commonly associated withbattery DC voltage ranges,220-240 Vis single-phase class, and380-415 Vrepresentsrated voltage, not the full acceptable upstream range.
質問 # 17
What is a primary function of DCIM (Data Center Infrastructure Management) software in relation to smart modules like those controlled by ECC800-Pro?
正解:A
解説:
DCIM platforms aggregate data from facility subsystems -- power, cooling, environmental sensors, and asset/space management -- providing centralized visualization, reporting, capacity planning, and analytics, often integrating with controllers like ECC800-Pro.
質問 # 18
What are the colors of indicators on the LCD panel of the MDU?
正解:B、C、D
解説:
On Huawei UPS systems (such as the UPS5000 series), the MDU LCD panel includes status indicators designed to provide an immediate visual understanding of the UPS operating condition and alarm severity.
The indicator system usesthree standard colors:green,yellow, andred.Greenindicates the UPS is operating normally and the power supply path is healthy.Yellowis used to show abnormal conditions that require attention, such as warnings or non-critical alarms, where the UPS can typically continue supplying power but O&M personnel should inspect and handle the issue within the required timeframe.Redindicates serious or critical conditions, such as major faults or alarms that may threaten continuous power supply or require urgent action according to operating procedures. These three colors align with the common Huawei alarm severity presentation logic on the UPS display and help technicians quickly judge whether the situation is normal, warning-level, or critical-level without entering deeper menus.Orangeis not used as an MDU indicator color in this context.
質問 # 19
......