Testpdf是一個可以成就很多IT人士的夢想的網站。Testpdf能為參加IT相關認證考試的考生提供他們想要的資料來助幫助他們通過考試。你還在為通過International Code Council 93-Tall-Mass-Timber-Buildings認證考試苦惱嗎?你有想過購買International Code Council 93-Tall-Mass-Timber-Buildings認證考試相關的課程來輔助你嗎?Testpdf可以為你提供這個便利,Testpdf提供的培訓資料可以有效地幫你通過認證考試。Testpdf提供的練習題幾乎真題是一樣的。有了Testpdf為你提供的精確的International Code Council 93-Tall-Mass-Timber-Buildings認證考試的練習題和答案,你可以以高分通過International Code Council 93-Tall-Mass-Timber-Buildings認證考試。
| Section | Objectives |
|---|---|
| Topic 1: Tall Mass Timber Building Code Provisions | - Fire Safety and Fire Resistance
- Special Inspection Requirements
|
>> 最新93-Tall-Mass-Timber-Buildings題庫資訊 <<
根據最新的擬真試題資訊,International Code Council 93-Tall-Mass-Timber-Buildings 認證擬真試題更新了,該擬真試題評估的適當性和資料的品質進行資料集成的積極性。本擬真試題已經幫助很多的考生順利通過 93-Tall-Mass-Timber-Buildings 考試,獲取證書。International Code Council 93-Tall-Mass-Timber-Buildings 認證擬真試題是有經驗的專家根據最新的考試指南編訂,經過很多次測驗適合全球考生使用,考生可以享受一年更新服務。考生可以參照最新的 93-Tall-Mass-Timber-Buildings 認證部分模擬試題。
問題 #44
Refer to the figure by clicking on the EXHIBIT button above.

The exterior wall section shown in the Figure provides the prescribed noncombustible protection required by which Construction Type?
答案:C
解題說明:
The illustrated configuration represents Type IV-C construction , so option C is correct. The distinguishing feature is the combination of noncombustible protection on the exterior face with an exposed CLT surface toward the interior.
IBC Section 602.4.3.1 requires the exterior side of combustible exterior walls in Type IV-C construction to have noncombustible protection providing a minimum assigned time of 40 minutes . Table 722.7.1(2) assigns exactly 40 minutes to one layer of 5/8-inch Type X gypsum board, matching the protection illustrated in Figure 66.
The decisive distinction is Section 602.4.3.2: mass timber elements in Type IV-C are permitted to be unprotected on the interior . This is fundamentally different from Type IV-A, where essentially all interior mass timber faces must be protected, and Type IV-B, where interior protection is generally required but limited areas may remain exposed under specific area and separation restrictions.
Type IV-HT does not use the Type IV-C protected-exterior/exposed-interior regulatory scheme.
References/Topics: 2021 IBC Sections 602.4.3, 602.4.3.1 and 602.4.3.2; Table 722.7.1(2), 5/8-inch Type X gypsum board = 40 minutes.
問題 #45
What fire-resistance rating is required for floors in Type IV-A, IV-B and IV-C construction?
答案:B
解題說明:
IBC Table 601 requires floor construction and associated secondary structural members in Types IV-A, IV-B, and IV-C construction to have a two-hour fire-resistance rating. Therefore, option B is correct.
This requirement applies to the complete floor assembly, not only the timber panel. The required two-hour performance may be established through the calculated fire resistance of the mass timber, the contribution of approved noncombustible protection, or a permitted combination of both. Any topping, protective membrane, connection protection, and edge condition that forms part of the approved rated design must be installed accordingly.
The ratings for other building elements should not be transferred to the floor. A three-hour rating applies to the primary structural frame and bearing walls of Type IV-A, but its floor construction remains two hours.
Type IV-B and Type IV-C floors also require two hours, even though those construction types permit different degrees of exposed mass timber.
The special inspector must verify panel dimensions, approved layup, protection layers, joints, penetrations, connections, topping thickness, and other details that influence the floor's rated performance.
References/Topics: 2021 IBC Sections 601 and 602.4; Table 601, floor construction and associated secondary structural members.
問題 #46
The building owner shall be responsible for each of the following for fire safety during construction except:
答案:B
解題說明:
The IFC does not require daily inspection documentation to be stored in a fire- and water-resistant safe.
Therefore, option C is the exception.
The owner or the owner's authorized agent must establish and maintain the required construction-site fire- prevention program and designate a site safety director. The site safety director is responsible for completing a daily fire-safety inspection covering the building and exterior project areas. The results must be documented, retained on-site until the certificate of occupancy is issued, and made immediately available to the fire code official upon request. Options A, B, and D accurately reflect these administrative requirements.
The purpose is not merely record retention. Daily inspections are intended to identify conditions such as obstructed fire apparatus access, blocked hydrants or fire department connections, exposed temporary wiring, improper hazardous-material storage, uncontrolled combustible debris, unavailable extinguishers, impaired standpipes, and deficient hot-work controls.
A special inspector is not automatically the site safety director. However, observations involving installed passive protection or unsafe construction conditions should be communicated through the approved reporting process. The owner remains accountable for implementing the site safety plan and maintaining the required documentation.
References/Topics: 2021 IFC Sections 3303.1 through 3303.3; site safety director and daily fire-safety inspection records.
問題 #47
Regarding water supply for the protection of buildings under construction, when combustible building materials of the building under construction are delivered to a site, the minimum fire flow provided shall be
_____ gpm.
答案:D
解題說明:
The required minimum fire flow is 500 gallons per minute , making option C correct.
2021 IFC Section 3313.1 requires an approved temporary or permanent water supply for fire protection to become available at specified stages of construction, including when combustible building materials arrive on the site. Section 3313.2 then establishes the specific requirement: when combustible building materials for the building under construction are delivered, a minimum fire flow of 500 gpm must be provided.
The hydrant supplying this flow must be located within 500 feet of the combustible building materials as measured along an approved fire apparatus access lane. If a single hydrant cannot provide the required coverage because of site configuration, additional hydrants are required.
The 500-gpm value in this question is the construction-stage minimum associated with combustible-material delivery. It should not be mistaken for the final required fire flow of the completed building. Depending on construction type, fire separation distance, building area, and subsequent phases of vertical construction, the required available water supply can be greater.
For mass timber projects, verifying this water supply before large timber packages arrive is a critical construction-phase fire-safety control.
References/Topics: 2021 IFC Sections 3313.1 and 3313.2; combustible building materials; minimum construction fire flow.
問題 #48
For Type IV-A, IV-B, and IV-C construction, each of the following materials on the exterior side of mass timber exterior walls is required to be noncombustible except:
答案:A
解題說明:
The code provides a specific combustible-material exception for qualifying water-resistive barriers , making option D correct. The exterior-protection provisions for Types IV-A, IV-B, and IV-C require the exterior side of mass timber walls to receive noncombustible protection with at least a 40-minute assigned protection time, and components of the exterior wall covering are generally required to be noncombustible.
A water-resistive barrier may be combustible only where it satisfies stringent fire-performance criteria.
Among those criteria, the 2021 IBC limits peak heat-release rate and total heat release under ASTM E1354 and establishes flame-spread and smoke-developed limits under ASTM E84 or UL 723. The provision therefore does not create a blanket exemption for arbitrary combustible membranes.
Insulation, exterior cladding, and architectural components forming part of the regulated exterior wall covering must comply with the applicable noncombustibility requirements unless some other express code allowance applies. The WRB is the specifically identified exception tested by this question.
During inspection, product identification and fire-test documentation should be checked rather than assuming that a membrane qualifies merely because it is marketed as a water-resistive barrier.
References/Topics: 2021 IBC Sections 602.4.1.1, 602.4.2.1 and 602.4.3.1; exterior wall protection and qualifying water-resistive barriers.