The content system of 93-Tall-Mass-Timber-Buildings exam simulation is constructed by experts. After-sales service of our 93-Tall-Mass-Timber-Buildings study materials is also provided by professionals. If you encounter some problems when using our products, you can also get them at any time. After you choose 93-Tall-Mass-Timber-Buildings preparation questions, professional services will enable you to use it in the way that suits you best, truly making the best use of it, and bringing you the best learning results. Our 93-Tall-Mass-Timber-Buildings Study Materials have a professional attitude at the very beginning of its creation for you to get your certification.
| Section | Objectives |
|---|---|
| Topic 1: Tall Mass Timber Building Code Provisions | - Special Inspection Requirements
- Type IV Construction
|
>> Exam 93-Tall-Mass-Timber-Buildings Answers <<
In the past few years, our 93-Tall-Mass-Timber-Buildings study materials have helped countless candidates pass the 93-Tall-Mass-Timber-Buildings exam. After having a related certification, some of them encountered better opportunities for development, some went to great companies, and some became professionals in the field. 93-Tall-Mass-Timber-Buildings Study Materials have stood the test of time and market and received countless praises. Through the good reputation of word of mouth, more and more people choose to use 93-Tall-Mass-Timber-Buildings study torrent to prepare for the 93-Tall-Mass-Timber-Buildings exam, which makes us very gratified.
NEW QUESTION # 72
Refer to the exhibit by clicking on the EXHIBIT button above.
In the detail shown, if the connections at the glulam beam and the steel plate required a fire-resistance rating of one (1) hour and the wood cover is designed per AWC Technical Report 10 to provide the entire one (1) hour of protection, the minimum required thickness for the wood block member providing protection for the bolt connections is _____ inches.
Answer: D
Explanation:
The required minimum wood protection thickness is 1.75 inches , making option B correct. AWC Technical Report No. 10 establishes a thermal-separation methodology for protecting steel connectors and fasteners with sacrificial wood cover. Because the question specifies that the wood cover itself must provide the entire 60- minute fire-protection period, the protection thickness must be calculated using the thermal-separation provisions rather than relying on residual fire resistance from the connector or steel plate.
TR10 applies a reduction to the protection contribution of the base wood layer. Its connection examples use the relationship in Section 4.4.1.3, with the required thermal protection time divided by 0.85. For a 60-minute requirement, back-calculating the prescribed nonlinear wood charring equation gives approximately 1.71 inches of required wood thickness. The practical minimum corresponding to the available choices is therefore
1.75 inches.
The principle is critical for special inspection: steel connection components have high thermal conductivity and must remain below the temperature limits assumed by the connection fire design. The inspector must verify actual wood-cover thickness, fastening, continuity, and any gaps before concealment.
References/Topics: AWC Technical Report No. 10, Sections 4.4.1.3 and 4.5; connection thermal separation; wood protection of steel connectors. TR10 demonstrates the same calculation methodology for wood-covered steel connections.
NEW QUESTION # 73
Materials acceptable for use in fire-protecting connections in Type IV-A construction includes each of the following except:
Answer: A
Explanation:
Steel plates are not themselves a fire-protective material for the connection; therefore, option A is the exception. Steel plates frequently form part of mass timber structural connections, but because steel is highly thermally conductive, exposed steel can rapidly transmit heat into fasteners and adjacent wood. Consequently, the steel connection components are normally the items that require protection , not the material relied upon to provide that protection.
AWC guidance recognizes wood cover, fire-rated gypsum board, and other approved protection materials as valid means of shielding structural connections. TR10 specifically provides calculation procedures and worked examples using sacrificial wood cover and Type X gypsum wallboard. An approved protective coating can also be used where its documented fire-performance characteristics establish the required endurance under the approved design.
The distinction is important for inspection. A concealed steel plate does not automatically mean a protected connection. The special inspector must verify whether sufficient wood cover, gypsum protection, approved coating, or another engineered protection system surrounds the steel for the required duration. Hardware geometry, exposed edges, gaps, and penetrations can all materially affect thermal performance.
References/Topics: AWC Technical Report No. 10, protection of structural connections; 2021 IBC Section
2304.10.1; AWC guidance that connection protection can be provided by wood cover, gypsum board, or other approved material.
NEW QUESTION # 74
Buildings of Types IV-A, IV-B, and IV-C construction designed to be greater than six stories above grade plane shall meet which of the following requirements for fire safety practices during construction?
Answer: C
Explanation:
The 2021 IFC specifically requires standpipes to be provided in accordance with Section 3313 for Type IV-A, IV-B, and IV-C buildings designed to exceed six stories above grade plane. Therefore, option A is correct.
The code also requires a water supply for fire department operations, but it must be approved by the fire code official and fire chief; it is not described as a mandatory "portable water supply." This makes option B inaccurate. Where noncombustible protection is required, at least one layer-not two layers-must be installed on applicable building elements more than four levels below active mass timber construction before additional levels are erected. Option D therefore overstates the number of layers.
Required exterior wall coverings must similarly be installed more than four levels below active mass timber construction. Option C incorrectly substitutes two levels for the prescribed four-level threshold.
These provisions limit the amount of unprotected combustible construction exposed at one time and provide the fire department with usable suppression infrastructure as erection progresses. Inspection coordination should verify standpipe extension, hose-connection accessibility, water availability, the progression of passive protection, and exterior-wall covering installation.
References/Topics: 2021 IFC Section 3308.4 and Section 3313; fire safety during construction of tall mass timber buildings.
NEW QUESTION # 75
Given: Sealants or adhesives need not be provided where they are not a required component of a tested fire resistance rated assembly.
If a sealant is required, it must meet the requirement of ASTM:
Answer: B
Explanation:
A sealant required to resist air passage between qualifying mass timber elements must comply with ASTM C920. Therefore, option C is correct. ASTM C920 is the recognized specification for elastomeric joint sealants and establishes requirements for properties such as movement capability, adhesion, cohesion, hardness, weathering, and durability.
IBC Section 703.7 differentiates between the two materials: sealants must meet ASTM C920, while adhesives must meet ASTM D3498. Option D therefore applies to an adhesive rather than a sealant. ASTM E119 is the standard fire test used to establish the fire-resistance rating of structural members and assemblies; it does not serve as the product specification for the sealant. ASTM E114 is not the applicable standard under this provision.
The stated exception is important. Section 703.7 does not require an additional sealant or adhesive where it is not a required component of the tested fire-resistance-rated assembly. Where the approved assembly or code provision does require it, however, the specified product, location, joint preparation, backing material, depth, width, and tooling must match the approved construction documents.
References/Topics: 2021 IBC Section 703.7; ASTM C920 sealants; ASTM D3498 adhesives; tested fire- resistance-rated assemblies.
NEW QUESTION # 76
Refer to the figure by clicking on the EXHIBIT button above.

In Type IV-B construction, unprotected portions of mass timber as shown in the Figure is limited to an area equal to not more than what percentage of the base floor area?
Answer: C
Explanation:
The highlighted exposed surfaces in this figure are mass timber wall surfaces . Under 2021 IBC Section
602.4.2.2.2, Exception 1.2, unprotected portions of Type IV-B mass timber walls, including attached columns, are permitted up to an area equal to 40 percent of the floor area in the applicable dwelling unit or fire area.
Option D is therefore correct.
This should be distinguished from the corresponding ceiling limitation. Unprotected mass timber ceilings, including attached beams, are limited to 20 percent of floor area. The larger 40-percent allowance applies specifically to wall exposure.
Where only wall surfaces are exposed, the allowable wall area is calculated directly from the base floor area.
For example, a 1,000-square-foot fire area would permit up to 400 square feet of exposed wall surface under this exception. However, Section 602.4.2.2.4 additionally requires unprotected wall portions to maintain the prescribed 15-foot separation from other applicable exposed wall or ceiling portions.
Where exposed walls and exposed ceilings occur together, the individual 40- and 20-percent limits cannot simply be maximized simultaneously; the mixed-exposure equation in Section 602.4.2.2.3 governs.
References/Topics: 2021 IBC Sections 602.4.2.2.2 through 602.4.2.2.4; Type IV-B wall exposure.
NEW QUESTION # 77
......
Constant improvements are the inner requirement for one person. As one person you can’t be satisfied with your present situation and must keep the pace of the times. You should constantly update your stocks of knowledge and practical skills. So you should attend the certificate exams such as the test International Code Council certification to improve yourself and buying our 93-Tall-Mass-Timber-Buildings Latest Exam file is your optimal choice. Our 93-Tall-Mass-Timber-Buildings exam questions combine the real exam’s needs and the practicability of the knowledge. The benefits after you pass the test International Code Council certification are enormous and you can improve your social position and increase your wage.