주제 1
  • Motor Control Centers (Low to Medium Voltage): Covers design standards, materials, enclosure types, breakers, amp capacity, cable entry, and grounding components for MCCs.
주제 2
  • Switchgear (Low & Medium Voltage): Covers design, construction, ratings, interlocks, wiring, enclosures, bus compartments, breakers, transformers, and metering for LV and MV switchgear.
주제 3
  • Examination Methods, Tools and Equipment: Covers the inspection techniques used in the field, including dimensional, visual, electrical testing, functional testing, and coatings inspections.
주제 4
  • Electrical Inspection Tools and Test Equipment: Covers the tools and test equipment used by inspectors to perform electrical source inspections.
주제 5
  • Electrical Skid Mounted Equipment: Addresses inspection of skid-mounted assemblies including hazardous location equipment, grounding, cable systems, control wiring, and applicable codes.
주제 6
  • Terms and Definitions: Covers the foundational terminology and definitions used throughout electrical source inspection work.
주제 7
  • Liquid-Immersed Transformers: Covers the design, construction, and applicable industry codes and standards for liquid-immersed transformers.

>> API API-SIEE인기자격증 덤프공부자료 <<

API-SIEE인기자격증 덤프공부자료 100% 합격 보장 가능한 덤프

많은 분들이 고난의도인 API관련인증시험을 응시하고 싶어 하는데 이런 시험은 많은 전문적인 관련지식이 필요합니다. 시험은 당연히 완전히 전문적인 API-SIEE관련지식을 터득하자만이 패스할 가능성이 높습니다. 하지만 지금은 많은 방법들로 여러분의 부족한 면을 보충해드릴 수 있으며 또 힘든 API시험도 패스하실 수 있습니다. 혹은 여러분은 전문적인 Source Inspector Electrical Equipment관련지식을 터득하자들보다 더 간단히 더 빨리 시험을 패스하실 수 있습니다.

최신 ICP Programs API-SIEE 무료샘플문제 (Q110-Q115):

질문 # 110
What document provides information on design and installation of electrical systems for fixed and floating offshore petroleum facilities for unclassified and Class I, Zone 0, Zone 1 and Zone 2 locations?

정답:C


질문 # 111
The highest voltage rating on a piece of medium voltage equipment is the:

정답:D

설명:
The correct answer isA, basic impulse level. On medium voltage equipment, thebasic impulse level BILis the highest voltage-related rating normally associated with the insulation system. BIL represents the ability of the equipment insulation to withstand a specified high-voltage impulse, such as a lightning surge or switching surge, without failure. It is therefore a dielectric withstand rating that is higher than the equipment's normal operating or system voltage and is used to define insulation coordination for the equipment.
The other choices are not the best answer.Nominal voltageidentifies the intended system operating voltage class, but it is not the highest voltage-related rating.AC high potentialandDC high potentialare test voltages used during dielectric testing, not the principal nameplate rating that defines the equipment's insulation impulse withstand capability. In source inspection of switchgear and other medium voltage assemblies, the inspector verifies that the equipment ratings, including voltage class, insulation level, and test records, agree with the purchase specification and applicable standards.
Because BIL expresses the highest recognized insulation withstand rating among the listed options,Ais the verified answer.


질문 # 112
Metallic shielding components such as tapes, wires, or braids shall be connected to a:

정답:B

설명:
The correct answer isA. Metallic shielding components in cables, such asshield tapes, drain wires, metallic braids, or similar conductive shielding layers, are connected to theequipment grounding system, commonly through anequipment grounding busbaror other approved grounding termination point. The purpose of this connection is to provide a low-impedance path for induced voltages, capacitive charging current, noise, and fault-related currents, while also helping reduce electromagnetic interference and maintaining personnel safety.
In source inspection and quality surveillance of electrical systems, correct shield termination is important because improper grounding can lead to noise problems, unreliable signal performance, unsafe touch potentials, or ineffective fault-current control. The inspector therefore checks that cable shields and associated metallic components are terminated in accordance with the approved drawings, cable schedules, and project grounding requirements.
The other options are incorrect. Aceramic insulatordoes not provide the required grounding path. Alow voltage connectoris too generic and is not the intended grounding termination. Atransformer center tapis a system neutral point, not the correct destination for cable metallic shielding. Therefore, the proper connection point is theequipment grounding busbar.


질문 # 113
According to NEMA ICS 2, a provision for pad locking shall be provided:

정답:B

설명:
The correct answer isB. UnderNEMA ICS 2for motor controllers and combination starters, the required provision forpadlockingis associated with theexternal operating handle. This arrangement allows the disconnecting means or operating mechanism to be secured in the desired position, typically for safety isolation and lockout purposes during maintenance or inspection. It is a functional safety feature tied directly to operation of the controller, not merely to enclosure access.
The other options are not the standard requirement in this context. Padlocking thedoor,wireway, orrear doormay be used in some installations for security or restricted access, but those are not the specific NEMA ICS 2 provisions identified for the controller operating mechanism itself. The standard intent is to ensure that the operating handle can be locked so the equipment cannot be unintentionally operated while personnel are working on or near it.
From an API source inspection perspective, this falls under verification ofMCC construction details, safety features, interlocks, and compliance with applicable referenced standardsduring shop inspection and quality surveillance. Therefore, the correct answer ison the external operating handle, which makesoption Bthe verified answer.


질문 # 114
What is the process that aims to find potential defects in a product before it is released for delivery?

정답:D

설명:
The correct answer isAbecauseinspectionis the activity specifically directed at identifying defects, nonconformities, damage, incomplete work, or deviations from specified requirements before the product is accepted and released for shipment or delivery. In the API source inspection context, inspection is a focused verification activity carried out during manufacturing and at final stages to confirm that the equipment conforms to approved drawings, purchase specifications, code requirements, and inspection and test plans. It is therefore the most direct process for finding product defects before handover.
Quality controlis broader than inspection. It includes inspection, testing, review of records, and other operational techniques used to verify product quality.Quality assuranceis even broader and more preventive; it focuses on the quality system, procedures, planning, and confidence that quality requirements will be met.
Examinationis too general and is not the best formal answer in source inspection terminology.
From an API perspective, the source inspector's practical role is to witness, verify, document, and report conformance and nonconformance. That makes inspection the primary defect-finding activity before delivery.


질문 # 115
......

API인증API-SIEE시험에 도전해보려고 없는 시간도 짜내고 거금을 들여 학원을 선택하셨나요? 사실 IT인증시험은 보다 간단한 공부방식으로 준비하시면 시간도 돈도 정력도 적게 들일수 있습니다. 그 방법은 바로Itcertkr의API인증API-SIEE시험준비덤프자료를 구매하여 공부하는 것입니다. 문항수도 적고 시험예상문제만 톡톡 집어 정리된 덤프라 시험합격이 한결 쉬워집니다.