93-Tall-Mass-Timber-Buildings 93-Tall-Mass-Timber-Buildings answers real questions can help candidates have correct directions and prevent useless effort. If you still lack of confidence in preparing your exam, choosing a good International Code Council 93-Tall-Mass-Timber-Buildings Answers Real Questions will be a wise decision for you, it is also an economical method which is saving time, money and energy.
| Section | Objectives |
|---|---|
| Tall Mass Timber Building Code Provisions | - Structural and Connection Requirements
- Special Inspection Requirements
|
>> Sample 93-Tall-Mass-Timber-Buildings Questions <<
Since our 93-Tall-Mass-Timber-Buildings study guide have veried versions which contain the PDF, Softwate and APP online, you can study whenever you are or even offline state according to their different merits. In addition, Our 93-Tall-Mass-Timber-Buildings training quiz will be very useful for you to improve your learning efficiency, because you can make full use of your all spare time to do test. It will bring a lot of benefits for you beyond your imagination if you buy our 93-Tall-Mass-Timber-Buildings Study Materials.
NEW QUESTION # 13
Which of the following requires continuous special inspection?
Answer: A
Explanation:
Adhesive anchors installed horizontally to resist sustained tension loads require continuous special inspection.
Therefore, option D is correct.
Continuous special inspection means that the special inspector must be present during the performance of the regulated work. This heightened oversight is necessary because horizontal or upwardly inclined adhesive- anchor installations resisting sustained tension are sensitive to installation variables such as borehole cleaning, adhesive proportioning, mixing, placement, embedment depth, temperature, cure time, and prevention of adhesive loss before curing. A concealed installation defect can substantially reduce long-term tension capacity.
The other listed activities are generally subject to periodic inspection under the mass timber special-inspection provisions. Periodic inspection allows the inspector to observe the work intermittently at appropriate stages rather than remaining present throughout the entire operation. Bolted connections, concealed mass timber connections, and anchorage of mass timber construction to deep foundation systems must still be inspected, but the code does not automatically designate each of those activities as continuous.
The inspector should also verify installer certification where required, approved adhesive-anchor evaluation documentation, expiration dates, storage conditions, drilling method, hole dimensions, and compliance with the approved structural documents.
References/Topics: 2021 IBC Sections 1705.3 and 1705.5.3; Table 1705.3; continuous inspection of adhesive anchors under sustained tension.
NEW QUESTION # 14
Refer to the exhibit by clicking on the EXHIBIT button above.
Given: The connections between the glulam beam and CLT panels all require a fire-resistance rating of 2 hours, and wood cover is designed per AWC Technical Report 10 to provide the entire 2 hours of protection.
The bearing area between the CLT and glulam is the minimum required.
What are the minimum dimensions, in inches, for the wood block shown in red?
Answer: A
Explanation:
Under the illustrated connection detail, the minimum wood-block dimensions are 3 inches by 3 inches.
Therefore, option C is correct.
The block is part of the sacrificial wood-cover system used to protect the connection for the full two-hour fire- resistance period. It must provide sufficient timber beyond the protected connection region to account for calculated charring and the increased exposure that can develop at the interface between abutting wood members. Because the problem states that the CLT-to-glulam bearing area is already the minimum required, the primary members do not provide surplus material that can be credited as additional protection at that edge.
AWC connection-fire-design guidance requires the protective geometry to remain effective after the calculated char front advances. Char contraction can open a gap at abutting edges and expose material deeper in the connection than would occur on an uninterrupted planar surface. The 3-inch-by-3-inch block maintains the required protective envelope for the stated two-hour condition.
This dimension is specific to the illustrated configuration and assumptions; it is not a universal minimum for every mass timber connection. The inspector must verify the approved detail rather than substitute nominal blocking based solely on field availability.
References/Topics: AWC Technical Report 10; AWC Fire Design Specification provisions for wood-cover protection and char contraction at abutting members.
NEW QUESTION # 15
What fire-resistance rating is required for floors in Type IV-A, IV-B and IV-C construction?
Answer: D
Explanation:
IBC Table 601 requires floor construction and associated secondary structural members in Types IV-A, IV-B, and IV-C construction to have a two-hour fire-resistance rating. Therefore, option B is correct.
This requirement applies to the complete floor assembly, not only the timber panel. The required two-hour performance may be established through the calculated fire resistance of the mass timber, the contribution of approved noncombustible protection, or a permitted combination of both. Any topping, protective membrane, connection protection, and edge condition that forms part of the approved rated design must be installed accordingly.
The ratings for other building elements should not be transferred to the floor. A three-hour rating applies to the primary structural frame and bearing walls of Type IV-A, but its floor construction remains two hours.
Type IV-B and Type IV-C floors also require two hours, even though those construction types permit different degrees of exposed mass timber.
The special inspector must verify panel dimensions, approved layup, protection layers, joints, penetrations, connections, topping thickness, and other details that influence the floor's rated performance.
References/Topics: 2021 IBC Sections 601 and 602.4; Table 601, floor construction and associated secondary structural members.
NEW QUESTION # 16
Regarding water supply for the protection of buildings under construction, when combustible building materials of the building under construction are delivered to a site, the minimum fire flow provided shall be
_____ gpm.
Answer: A
Explanation:
The required minimum fire flow is 500 gallons per minute , making option C correct.
2021 IFC Section 3313.1 requires an approved temporary or permanent water supply for fire protection to become available at specified stages of construction, including when combustible building materials arrive on the site. Section 3313.2 then establishes the specific requirement: when combustible building materials for the building under construction are delivered, a minimum fire flow of 500 gpm must be provided.
The hydrant supplying this flow must be located within 500 feet of the combustible building materials as measured along an approved fire apparatus access lane. If a single hydrant cannot provide the required coverage because of site configuration, additional hydrants are required.
The 500-gpm value in this question is the construction-stage minimum associated with combustible-material delivery. It should not be mistaken for the final required fire flow of the completed building. Depending on construction type, fire separation distance, building area, and subsequent phases of vertical construction, the required available water supply can be greater.
For mass timber projects, verifying this water supply before large timber packages arrive is a critical construction-phase fire-safety control.
References/Topics: 2021 IFC Sections 3313.1 and 3313.2; combustible building materials; minimum construction fire flow.
NEW QUESTION # 17
Which of the following provisions for mass timber used for interior exit and elevator hoistway enclosures is true?
Answer: C
Explanation:
Option A correctly applies the protection requirements for mass timber used in qualifying interior exit and elevator hoistway enclosures. Where a two-hour, or 120-minute, fire-resistance rating is required, the noncombustible protection must contribute not less than two-thirds of that required rating. Two-thirds of 120 minutes is 80 minutes.
The 2021 IBC provisions for Type IV-A require interior mass timber surfaces to be protected with compliant noncombustible materials. The assigned protection time is determined under Section 722.7 and cannot be less than the applicable minimum. Option B is incorrect because 40 minutes would provide only one-third of a two-hour rating; Type IV-B protected mass timber generally requires at least 80 minutes for a two-hour element. Option C does not correctly describe the special protection path applicable to mass timber exit and hoistway enclosures. Option D is also incorrect because Type IV-HT is not governed by the tall mass timber enclosure provision stated in the question.
The inspector must verify the total assigned protection time, membrane type, number of layers, fastening, joints, corners, penetrations, and continuity on both required faces of the enclosure.
References/Topics: 2021 IBC Sections 602.4, 602.4.1.2 and 722.7.1; protection of mass timber shaft and exit enclosures.
NEW QUESTION # 18
......
Hence, memorizing them will help you get prepared for the International Code Council 93-Tall-Mass-Timber-Buildings examination in a short time. The product of Exam4Tests comes in PDF, desktop practice exam software, and 93-Tall-Mass-Timber-Buildings (93-Tall-Mass-Timber-Buildings) web-based practice test. To give you a complete understanding of these formats, we have discussed their features below.