93-Tall-Mass-Timber-Buildings試験の参考資料では、無料の試用版をダウンロードできます。試用版を使用して、知りたい情報を入手できます。 93-Tall-Mass-Timber-Buildings学習教材の試用版をダウンロードした後、目的の選択を行うことができるお気に入りの93-Tall-Mass-Timber-Buildings試験準備だけでなく、お好きなバージョンも簡単に選択できます。 93-Tall-Mass-Timber-Buildings学習資料では、すべてのユーザーが製品を理解し、本当に必要なものを入手できるようにしています。 93-Tall-Mass-Timber-Buildings学習教材は非常に理解しやすいので、あなたが誰であっても、ここで欲しいものを見つけることができます。
| Section | Objectives |
|---|---|
| Structural & Connection Inspection | - Connection Design and Protection - Framing and Structural Elements |
| Mass Timber Materials | - CLT, Glulam, NLT, SCL and Engineered Wood Products |
| Inspection Duties & Documentation | - Statement of Special Inspections - Inspection Reporting and Compliance Verification |
| General & Construction Types | - Construction Classification — Type IV-A, IV-B, IV-C
|
| Construction Fire Safety | |
| Fire-Resistance & Protection | - Fire-Resistance-Rated Assemblies - Noncombustible Protection & Encapsulation - Concealed Spaces Protection |
>> 93-Tall-Mass-Timber-Buildings認定試験 <<
急速な市場の発展に伴い、学習者が試験の準備に役立つ93-Tall-Mass-Timber-Buildingsガイド急流を販売する企業やWebサイトが増えています。あなたが以前に知っていたなら、当社の教材が学生やビジネスマンに関係なく候補者に非常に人気があることを見つけることは難しくありません。 93-Tall-Mass-Timber-Buildings試験トレントの購入を歓迎します。古いsayingにもあるように、クライアントは神です!サービスが一番です! 93-Tall-Mass-Timber-BuildingsガイドBraindumpsは、限られた時間の試験とオンラインエラー修正をシミュレートでき、24時間年中無休のサービスを提供しています。93-Tall-Mass-Timber-Buildings試験Torrentは、試験を準備するための最良かつ賢明な選択です。
質問 # 46
Regarding water supply for the protection of buildings under construction, when combustible building materials of the building under construction are delivered to a site, the minimum fire flow provided shall be
_____ gpm.
正解:B
解説:
The minimum required fire flow is 500 gallons per minute. Therefore, option C is correct.
Under 2021 IFC Section 3313.2, an approved water supply must be available when combustible building materials for the building under construction are delivered to the project site. The hydrant supplying the required flow must be located within the prescribed distance of the combustible materials as measured along an approved fire apparatus access route. Where one hydrant cannot provide coverage to all combustible material locations, additional hydrants are required.
The 500-gpm requirement is the initial minimum associated with the delivery of combustible building materials. It should not be confused with the potentially greater fire-flow requirements applicable after vertical construction of a Type III, IV, or V building begins. Depending on fire separation distance and the building's calculated final fire-flow demand, a larger supply may be required under subsequent provisions.
Options A and B provide inadequate suppression capacity. Option D is not the baseline amount prescribed for the condition stated in the question. Inspectors and site safety personnel should verify that the water source is operational and accessible before substantial quantities of mass timber arrive on-site.
References/Topics: 2021 IFC Sections 3313.1 and 3313.2; construction-site water supply and combustible building materials.
質問 # 47
The International Building Code requires cross-laminated timber (CLT) to be manufactured and identified in accordance with which standard?
正解:D
解説:
The governing standard is ANSI/APA PRG 320, Standard for Performance-Rated Cross-Laminated Timber.
Therefore, option A is correct. The 2021 IBC requires structural glued cross-laminated timber to be manufactured and identified in accordance with PRG 320, and Type IV provisions require CLT to bear a label demonstrating conformity with that standard.
PRG 320 addresses essential manufacturing and qualification requirements, including panel construction, layup, structural performance, adhesive qualification, dimensional tolerances, product marking and quality assurance. Product identification is particularly important to the special inspector because visual similarity alone does not establish that a panel is code compliant.
DOC PS 2 applies primarily to wood structural panels such as plywood and oriented strand board and is not the manufacturing standard for CLT. ANSI/AITC or ANSI/APA A190.1 applies to structural glued-laminated timber, commonly called glulam. ASTM D5055 covers the establishment and monitoring of structural capacities for prefabricated wood I-joists.
The inspector should verify that CLT panels retain legible identification and that the manufacturer, grade, layup and panel designation correspond to the approved construction documents.
References/Topics: 2021 IBC Sections 602.4 and 2303.1.4; Chapter 35; ANSI/APA PRG 320-2019.
質問 # 48
Where Type X gypsum board serves as noncombustible protection for interior surfaces of wall and ceiling assemblies, all of the following code provisions are correct except:
正解:C
解説:
Option D is the incorrect statement. IBC Section 722.7.2.1 requires the panel edges of the face layer , rather than the base layer, to be taped and finished with joint compound. Fastener heads on the face layer must also be covered with joint compound.
The other three provisions accurately reproduce the code. Each gypsum-board layer must be secured with Type S drywall screws long enough to penetrate the mass timber at least 1 inch when driven flush. Screws for the base layer are installed at 12 inches on center in both directions . Subsequent layers use the same general spacing but are offset from screws in the preceding layer. In addition, the panel edges of each succeeding layer must be offset 18 inches from the panel edges of the previous layer.
These details are not merely workmanship recommendations. They form part of the installation conditions under which the protection contributions in Table 722.7.1(2) can be credited.
References/Topics: 2021 IBC Section 722.7.2.1, Items 1-9; fastening, panel-edge offset, and finishing of Type X gypsum protection.
質問 # 49
Which of the following requires periodic special inspection of mass timber elements?
正解:B
解説:
Concealed connections in Type IV-C construction require periodic special inspection under 2021 IBC Table
1705.5.3, making option B correct.
The mass timber special-inspection table specifically applies to mass timber elements in Types IV-A, IV-B, and IV-C . Among the activities listed for periodic inspection are bolted connections, concealed connections, erection of mass timber construction, screw installation, verification of required predrilling, and several other connection-related installation characteristics.
Options A and C are incorrect because they specify Type IV-HT. Table 1705.5.3 is expressly scoped to Types IV-A, IV-B, and IV-C rather than Type IV-HT. Option D involves a listed Type IV-A activity, but its inspection frequency is wrong: adhesive anchors installed horizontally or upwardly inclined to resist sustained tension loads require continuous , not periodic, special inspection.
For concealed connections, inspection must occur while the relevant components remain observable. Once CLT panels, wood cover, gypsum protection, or finishes hide the connection, critical installation details may no longer be verifiable without destructive removal.
References/Topics: 2021 IBC Section 1705.5.3 and Table 1705.5.3, Required Special Inspections of Mass Timber Construction.
質問 # 50
Given: A building of Type IV-B construction is designed to be greater than six stories above grade plane.
At least one layer of required noncombustible protection shall be installed on all of the following building elements except _____ on all floor levels more than four levels below active mass timber construction before erecting additional floor levels during construction.
正解:D
解説:
The intended code exception is shafts and vertical exit enclosures , making option B correct. The governing construction-phase provision is 2021 IFC Section 3303.5, which applies to buildings of Types IV-A, IV-B, and IV-C designed to exceed six stories above grade plane.
Where Section 602.4 of the IBC requires noncombustible protection, at least one layer must be installed on building elements located on floor levels-including mezzanines-more than four levels below active mass timber construction before additional floor levels can be erected. The provision is intended to prevent a tall mass timber project from accumulating an excessive number of substantially unprotected combustible stories during erection.
Section 3303.5 expressly states that shafts and vertical exit enclosures are not considered part of the active mass timber construction for application of this construction-progress requirement. Therefore, B is the examination answer.
Mezzanines are expressly included in the protected-level requirement. Required protection for floors, walls, and ceilings under IBC Section 602.4 progresses with construction subject to the IFC provision. The same section also requires standpipes, an approved water supply for fire department operations, and timely installation of required exterior wall coverings.
References/Topics: 2021 IFC Section 3303.5; 2021 IBC Section 602.4; fire safety during construction of tall mass timber buildings.